Has anybody ever used one of those venturi type vacuum pumps to evacuate their AC system?
yes
How much air volume do you need to run it?
alot
just ok
I only ever work on AC maybe once ever 5 years or so.
For that they're fine.
I think they say 75 psi.... That's not enough. To pull max vacuum I need 95 psi at my regulator before the vacuum pump. (50ft of 3/8 hose after regulator)
My 30 yr 2HP compresser can't quite make the air volume at 95psi. Gets to about 85psi, then maxes out with a 100% duty cycle.
So I needed to figure out when the compressor turns off. (118psi)
I'll turn the AC gauge set off. turn the air pressure down at the compressor and let the tank pressure built to 115psi, then turn the air pressure all the way up. Then open the valve at the gauge set again.
The tank air slowly bleeds down as the compressor can't keep it at 115psi. But I get about 5 minutes of 95psi output to the venturi pump. When it starts to drop below 95psi, gauge valve goes off and repeat above procedure.
If you have a big air compressor, you'll be fine, just adjust air pressure for max vacuum. (have the valves closed on the end of the gauge set hoses so you're only pulling a vacuum in the gauge set and gauge hoses)
If it matters, my vacuum pump is a 30yr robinair......